+1 610.524.8800

Inerting Control Systems  |  N2 Blanketing Systems

Engineered solutions for inerting control / tank blanketing

For process safety, quality control, and efficiency

Using N2 or other gases to create inert gas atmospheres is a widely used practice that reliably protects against flash fires and explosions. In addition to the safety benefits, our systems are used to improve product quality by preventing contact with oxygen and moisture and to lower production costs and increase profitability by efficiently controlling inert gas usage.

Applications for inerting control systems (ICS) can be found in many steps of the manufacturing process, ranging from production and product storage to packaging and transportation.

  • Oxidant concentration reduction is recommended in NFPA 69 as a method to prevent combustion of flammable materials
    Benefit: Ensures safe operation of process systems that involve flammable materials (process safety)
  • Using nitrogen to reduce oxygen levels makes certain that product quality remains at the highest level
    Benefit: Reduces the risk of product degradation for products that are affected by exposure to oxygen (product quality)
  • Adding nitrogen only when needed can dramatically reduce inert gas usage spending
    Benefit: Makes nitrogen usage more economical (cost savings)
  • N2 inerting of flammable and combustible liquids to ensure safe handling
    • The ICS maintains the O2 content in the vessel vapor space to a value that is less than the concentration needed to support combustion (limiting oxidant concentration – LOC, NFPA 69)N2 inerting of powders to prevent combustible dust explosions
  • Concentration control of inert environments to improve handling of polymerization-inhibited materials
  • N2 inerting to maintain product quality in materials that are sensitive to air, oxygen, and moisture
  • N2 blanketing to reduce VOC emissions
  • Concentration control / inerting control to reduce inert gas usage
    • Adding N2 and inert gas only as needed reduces gas usage spending (when compared with continuous purge, time-volume, and pressurization techniques)
  • Oxygen sensor
  • Measures the oxygen content in the conditioned gas stream
  • Sample conditioning package
  • Delivers a clean dry sample to the sensor
  • Removes varying amounts of entrained vapors, dusts, and contaminants from the sample gas stream
  • Pre-conditioning components:
  • Designed to prevent process vapors, mists, condensed liquids, or dusts from affecting the accuracy and reliability of the O2 sensor
  • O2 analyzer
  • Provides continuous real-time O2 monitoring and control
  • Controls the flow of inert gas into the process or vapor space by turning the inerting control valve on and off
  • Includes user-adjustable alarms and inert gas control functions with relay outputs

Wall-mount Mini-ICS analyzer installed in non-hazardous area

Single point monitoring with user-adjustable setpoints and relay outputs Inerting Control Systems Wall-mount Mini-ICS analyzer installed in non-hazardous areaSingle point monitoring with user-adjustable set points and relay outputs


Wall-mount Mini-ICS analyzer installed in non-hazardous area

Single point monitoring with user-adjustable setpoints and relay outputs; remote indicator lamp station Inerting Control Systems Wall-mount Mini-ICS analyzer installed in non-hazardous areaSingle point monitoring with user-adjustable setpoints and relay outputs; remote indicator lamp stationInerting Control Systems


Sampler with intrinsically safe transmitter (4-20 mA output)

Single point monitoring with DCS operated inerting control valve Inerting Control Systems Sampler with intrinsically safe transmitter (4-20 mA output)Single point monitoring with DCS operated inerting control valve


Wall-mounted Model 1100 installed in non-hazardous area

Single point monitoring with DCS operated inerting control valve Inerting Control Systems Wall-mounted Model 1100 installed in non-hazardous areaSingle point monitoring with DCS operated inerting control valve


Wall-mounted explosion proof Mini-ICS installed in hazardous area

Single point monitoring with user-adjustable set points and relay outputs Inerting Control Systems Wall-mounted explosion proof Mini-ICS installed in hazardous areaSingle point monitoring with user-adjustable setpoints and relay outputs


Multi-vessel N2 inerting control system

Multi-point monitoring with sample source selector valves Inerting Control Systems Multi-vessel N2 inerting control systemMulti-point monitoring with sample source selector valves


Sample selector valve configuration

Multi-point monitoring with sample source selector valves Inerting Control Systems Sample selector valve configurationMulti-point monitoring with sample source selector valves


Wall-mounted explosion proof Oxytron installed in hazardous area

Single channel monitoring with user-adjustable setpoints and relay outputs; dual sensor configuration Inerting Control Systems Single channel monitoring with user-adjustable setpoints and relay outputs; dual sensor configuration


Wall-mounted explosion proof Oxytrons installed in non-hazardous area

Multi-channel monitoring with user-adjustable setpoints and relay outputs Inerting Control Systems Wall-mounted explosion proof Oxytrons installed in non-hazardous area Multi-channel monitoring with user-adjustable set points and relay outputs